Appendix: Technical Specifications

30

Measurement Specifications

Accuracy

Parameter

Full Scale @

Input Range

%

Reading

%

FS

Conditions

Range

Voltage V1-V3

(L-n)

120 x PT ratio

@ 120V

0.05

±0.0

5

1% up to 140%

0 up to 999,000 V

Voltage V4

(calculated)

120V x PT ratio

@ 120V

±0.5

5% up to 140%

Voltage V1-V3

(L-n)

69 x PT ratio

0.1

±0.0

5

1% up to 140%

0 up to 999,000 V

Voltage V4

(calculated)

69 x PT ratio

±0.5 5% up to 140%

Line current

I1- I4

CT primary

current

±0.06 ±0.0

6

1% up to 120% In 0 up to 20,000 A

Fault current

I1- I4

CT primary

current

±0.5

-

120%- 1000% In

0 up to 100,000 A

Active power

3xV

FS×CT/1000

0.2 0.02

|PF| ≥ 0.5 *

-10,000,000 kW to
+10,000,000 kW

Reactive power 3xV

FS×CT/1000

0.3 0.04

|PF| ≤ 0.9 *

-10,000,000 kvar to
+10,000,000 kvar

Apparent

power

3xV

FS×CT/1000

0.2 0.02

|PF| ≥ 0.5 *

0 to 10,000,000 kVA

Power factor

1.000 0.2

|PF|

≥ 0.5, I ≥ 2%

FSI

-0.999 to +1.000

50 Hz

-

±0.0

2

40-65 Hz

40.00 up to 64.99 Hz

Frequency

60 Hz

-

±0.0

2

45- 70 Hz

45.00 up to 69.99 Hz

Total Harmonic

Distortion, THD

V (I), %Vf
(%If)

999.9 1.5

0.1

THD ≥ 1%,
V (I) ≥ 10% FSV

(FSI)

0 to 999.9

Total Demand
Distortion,

TDD, %

100

1.5

TDD ≥ 1%,
I ≥ 10% FSI

0 to 100

Active energy
Import &

Export

ANSI C12.20, Class 10/20, Acc. Class

0.2S

0 to 999,999.999 MWh

Reactive

energy
Import &
Export

Class 0.5S under conditions as per

IEC 62053-22:2003 @ 0≤ |PF| ≤ 0.9

0 to 999,999.999 Mvarh

Apparent
energy

Class 0.2S under conditions as per
IEC 62053-22:2003

0 to 999,999.999 MVAh

Symmetrical
components

Voltage FS
Current FS
Current FS

1.0
1.0
3.0

10% - 120% FS
10% - 200% FS
200% -

3000%FS

Phasor angles

1 degree

* @ 80% to 120% of voltage FS, 2% to 200% of current FS, and frequency 50/60 Hz
PT - external potential transformer ratio