beautypg.com

Electrical installation, Voltage inputs, Current inputs – SATEC EM920 Installation Manual User Manual

Page 14: Ground input, Typical installation, Form 9 wiring configurations, Figure 6: form 9 typical electrical installation, Table 1: wiring configuration

background image

Chapter

8

Electrical Installation

Before installing, ensure that all incoming power sources are

shut OFF. Failure to observe this practice can result in serious
or even fatal injury and damage to equipment.

Voltage Inputs

There are 3 AC Y-connected voltage inputs of 207VAC (phase-to-phase) and neutral, via

socket meter blades.
The EM920 Power Supply Inputs are the same as the Voltages Inputs

Current Inputs

There are 4 current inputs up to 50A, connected to external CT’s via socket meter blades.

Ground Input

Make sure the EM920 socket is properly connected to ground

Typical Installation

Before installing, ensure that all incoming power sources are

shut OFF and are protected with a slow blow fuse of 2A (SW1
and SW3), and short the current inputs (SW2)

Figure 6: FORM 9 Typical Electrical Installation

FORM 9 Wiring Configurations

There are six wiring configurations shown in Figures 7, 8, 9, 10, 11, 12;

W i r i n g C o n f i g u r a t i o n

Wiring Setup

See Figure:

4-wire WYE 3-element using 3 CTs

4Ln3

7

4-wire WYE 3-element connection using 3 PTs, 3 CTs

4Ln3

8

4-wire 3-element delta using 3 CTs

4LL3

9

4-wire 3-element delta connection using 3 PTs, 3 CTs

4LL3

10

3-wire 2-element connection using 2 CTs

3OP3

11

3-wire 2-element connection using 2 PTs, 2 CTs

3OP3

12

Table 1: Wiring Configuration

See parameter setup instructions in the Operation Manual