Appendix: Technical Specifications

24

Appendix: Technical Specifications

Inputs Ratings

AC Voltage inputs Va, Vb, Vc and Vref - 50/60Hz

High input impedance =
10M

Voltage rating:
57.73 up to 120 Volts (L-N), 100 to

207 Volts (L-L)

Voltage range
Crest factor >2 [V

L-N

x 1.2 x 2]

0 -144 V r.m.s,
peak up 288V (for PQ)

Maximum Line to Line voltage

500 V r.m.s

Temporary over voltage between live
conductors and earth
Transient over voltage between live

conductors and earth (optional, from
15 µs up to ms)

240 V r.m.s

1.5 kV peak

Starting voltage

1

0.1%U

n

Burden per phase

< 0.2 VA

Overload withstand for 1 minute

phase-to-ground (ANSI C12.1 & IEC
62053-22, protective class II)

4000V r.m.s

Rated impulse voltage
(ANSI C12.1 & IEC 62052-11,
protective class II)

6000V peak

Reference voltage

U

n

57.73V up to

120V L-N (via PT)

Terminals for wires size

Blades (Socket meter

standard – C12.10)

Ground input

Terminals for wires size

According to Socket meter
standard – C12.10

AC Current inputs 3 (4 optional) Galvanic isolated Inputs

Current class Imax

10A & 20A

Maximum measurable short circuit

current (Isc)

10 x I

n

Burden per phase (In = 5 A)

< 0.2 VA

Starting current (I1, I2, I3) – average
Starting current (I1, I2, I3) – real

time

0.2% I

n

1.0% I

n

Over current withstand for 1 s non-

recurring

50 x I

n

Isolation

4000V r.m.s

Terminals for wires size

Blades (Socket meter
standard – C12.10)

Reference Current
Basic model In =

5 A
(TA = 2.5A)

3 (4 optional) Galvanic isolated Inputs FORM 9 (39 optional)

1

Starting voltage, interruptions and dips measurement applicable only with installed APS