User selectable options menu, 9 user selectable options menu – SATEC C191HM User Manual
Page 44

Chapter 4 Setup Menus
35
4.9 User Selectable Options Menu
This menu allows you to change options which relate to the instrument features
and functionality. Table 4-10 lists all available options with their code names and
applicable ranges.
To select an option:
Press to activate the middle window, and then use the
up/down arrow keys to scroll to the desired option.
To change the selected option:
Press to activate the lower window.
Use the up/down arrow keys to set the desired value.
Press to store your new setting or to leave the
previous setting unchanged.
To quit the display setup menu:
From the middle window, press or .
Table 4-10 User Selectable Options (
∗ default setting)
Code
Parameter
Options
Description
P.cAL
Power calculation
mode
rEAc*
nAct
Using reactive power
Using non-active power
roLL
Energy roll value
10.E4
10.E5
10.E6
10.E7
10.E8*
10,000 kWh
100,000 kWh
1,000,000 kWh
10,000,000 kWh
100,000,000 kWh
Ph.En
Phase energy
measurements
diS*, En
Enables/disables measurements of
energies per phase
Power calculation mode (P.cAL):
Mode 1: Reactive power calculation (rEAc)
Active power P and reactive power Q are measured directly and apparent power
S =
√ P
2
+ Q
2
Mode 2: Non-active power calculation (nAct)
Active power is measured directly, apparent power S = V
× I (where V, I - rms
voltage and currents) and non-active power N =
√ S
2
-
P
2
Mode 1 is recommended for electrical networks with low harmonic distortion (voltage
THD
< 5%, current THD < 10%); Mode 2 is recommended for all other cases.