SATEC C191HM User Manual
Page 39

Chapter 4 Setup Menus
30
Code
Parameter
Unit
Range
A. PF.Ld
Low total PF Lead
0 to 1.000
Average Auxiliary Measurements
Ar neU.C
High neutral current
A
0 to Imax
Ar Hi.Fr
High frequency
Hz
0 to 100.00
Ar Lo.Fr
Low frequency
Hz
0 to 100.00
Present Demands
Hi d.U1
High volt demand L1
V
0 to Vmax
Hi d.U2
High volt demand L2
V
0 to Vmax
Hi d.U3
High volt demand L3
V
0 to Vmax
Hi d.C1
High ampere demand L1
A
0 to Imax
Hi d.C2
High ampere demand L2
A
0 to Imax
Hi d.C3
High ampere demand L3
A
0 to Imax
Hi d.P
High block interval kW demand
kW
0 to Pmax
Hi d.S
High block interval kVA demand
kVA
0 to Pmax
Hi Sd.P
High sliding window kW demand
kW
0 to Pmax
Hi Sd.S
High sliding window kVA demand
kVA
0 to Pmax
Hi Ad.P
High accumulated kW demand
kW
0 to Pmax
Hi Ad.S
High accumulated kVA demand
kVA
0 to Pmax
Hi Pd.P
High predicted sliding window kW demand kW
0 to Pmax
Hi Pd.S
High predicted sliding window kVA demand kVA
0 to Pmax
High Voltage Harmonic Distortions on any Phase
Hd03.U
High voltage harmonic H03
%
0 to 100.00
Hd05.U
High voltage harmonic H05
%
0 to 100.00
...
...
Hd39.U
High voltage harmonic H39
%
0 to 100.00
High Current Harmonic Distortions on any Phase
Hd03.C
High current harmonic H03
%
0 to 100.00
Hd05.C
High current harmonic H05
%
0 to 100.00
...
...
Hd39.C
High current harmonic H39
%
0 to 100.00
For parameter limits, see notes to Table 4-4.
The setpoint is operated when the actual phase sequence does not match the indicated
normal phase rotation.
The actual frequency range is 45.00 - 65.00 Hz.
When the 4LN3 or 3LN3 wiring mode is selected, the voltages will be line-to-neutral; for
any other wiring mode, they will be line-to-line voltages.