SATEC C191HM User Manual
Page 37

Chapter 4 Setup Menus
28
Setpoint action The action to be triggered is operation of relay #1.
To select a setpoint:
Scroll to the desired setpoint using the up/down arrow keys.
To view the setup options for the setpoint:
Press to activate the middle window.
Use the up/down arrow keys to scroll to the desired setup option. The value
associated with this option is displayed in the lower window.
To change the selected setup option:
Press to activate the lower window.
Use the up/down arrow keys to scroll to the desired value.
Press to store the new value.
Press to leave the value unchanged.
To store your new setup for the setpoint:
From the middle window, press .
To quit the setpoint setup without changes:
From the middle window, press .
To quit the setpoints setup menu:
From the upper window, press or .
NOTES
1. If your instrument is not equipped with the optional relay, then these setup
parameters will not appear on the display.
2.
When you enter the setpoints setup menu at the protected level, monitoring setpoints
is temporarily suspended until you return to the main setup menu.
3.
Each time you select a new trigger parameter, the operate and release limits are set
by default to zero.
4.
You will not be able to store your setpoint setup to the instrument if a setpoint action
is directed to a relay allocated for pulsing.
5.
The setpoint action directed to a relay output can be overridden using commands
sent via communications. A relay can be manually operated or released. When the
relay reverts to normal operation, it is automatically returned under setpoint control.
SP 1
rEL.1
Act
SELECT
SELECT
ENTER
ENTER
ENTER
ESC
ESC
ESC