beautypg.com

Caution, Warning – Bryant SERIES A 355CAV User Manual

Page 15

background image

15

HORIZONTAL RIGHT

(SUPPLY--AIR DISCHARGE) APPLICATIONS

A horizontal right furnace application is where furnace blower is

located to the left of combustion and controls section of furnace,
and conditioned air is discharged to the right.

PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in property

damage.
Local codes may require a drain pan under entire furnace

and condensate trap when a condensing furnace is used in

an attic application or over a finished ceiling.

CAUTION

!

NOTE: In Canada, installations shall be in accordance with
current NSCNGPIC and/or local codes.
NOTE: The auxiliary junction box (J--box ) MUST be relocated
to opposite side of furnace casing. (See Fig. 14.) See Electrical
Connection section for J--box relocation.
Condensate Trap Location

CAP

PLUG

COLLECTOR BOX

DRAIN TUBE (BLUE &

WHITE STRIPED)

INDUCER HOUSING

(MOLDED) DRAIN

TUBE (VIOLET)

COLLECTOR BOX TUBE (PINK)

COLLECTOR BOX

DRAIN TUBE (BLUE)

COLLECTOR BOX

EXTENSION TUBE

CONDENSATE

TRAP

COLLECTOR BOX

TUBE (GREEN)

AUXILIARY “J” BOX RELOCATED HERE

A07279

Fig. 14 -- Horizontal Right Tube Configuration

The condensate trap must be removed from the factory--installed
blower shelf location and relocated in selected application

location as shown in Fig. 2 or 14.
To relocate condensate trap from the blower shelf to desired
location, perform the following:

1. Remove three tubes connected to condensate trap.
2. Remove trap from blower shelf by gently pushing tabs in-

ward and rotating trap.

CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal

injury or death.
Casing hole filler cap must be installed in blower shelf hole

when condensate trap is relocated to prevent combustion

products being drawn in from appliances in the equipment

room.

!

WARNING

3. Install casing hole filler cap (factory--supplied in loose

parts bag) into blower shelf hole where trap was removed.

4. Install condensate trap into right--hand side casing hole by

inserting tube connection tabs through casing hole and ro-
tating until tabs snap into locking position.

5. Fill unused condensate trap casing holes with plastic filler

caps (factory--supplied in loose parts bag).

UPFLOW OR DOWNFLOW

HORIZONTAL

FRONT

FRONT

LEVEL (0”)

TO 1/2” (13mm)

MAX

MIN 1/4” (7mm)

TO 1/2” (13mm)

MAX

A02146

Fig. 15 -- Proper Condensate Drainage

Condensate Trap Tubing
NOTE
: See Fig. 14 or tube routing label on main furnace door
to check for proper connections.

1. Collector Box Drain Tube

a. Remove factory--installed plug from LOWER collector

box drain tube (blue and white striped label).

b. Install removed clamp and plug into UPPER collector

box drain tube (blue label) which was previously connec-
ted to condensate trap.

c. Connect LOWER collector box drain tube (blue and

white striped label) to condensate trap. Tube does not
need to be cut.

d. Clamp tube to prevent any condensate leakage.

2. Inducer Housing Drain Tube

(a.)Remove factory--installed cap and clamp from

LOWER inducer housing drain connection.

(b.)Remove and discard UPPER (molded) inducer

housing drain tube which was previously con-
nected to condensate trap.

(c.)Install cap and clamp on UPPER inducer hous-

ing drain connection where molded drain tube
was removed.

(d.)Use inducer housing drain extension tube (violet

label and factory--supplied in loose parts bag) to

connect LOWER inducer housing drain connec-
tion to condensate trap.

(e.)Determine appropriate length, cut, and connect

tube to condensate trap.

(f.)Clamp tube to prevent any condensate leakage.

3. Relief Port Tube

Refer to Pressure Switch Tubing section for recommenda-
tions and procedures.

Condenste Trap Field Drain Attachment
Refer to Condensate Drain section for recommendations and

procedures.
Pressure Switch Tubing
One collector box pressure tube (pink label) is factory connected
to the pressure switch for use when furnace is installed in

UPFLOW or HORIZONTAL LEFT applications. This tube
MUST be disconnected and used for the condensate trap relief

port tube. The other collector box pressure tube (green label)

which was factory connected to the condensate trap relief port
connection MUST be connect to the pressure switch in

DOWNFLOW or HORIZONTAL RIGHT applications.

355C

A

V