7 Maintenance

7-2. Regular maintenance mode

- 57 -

RM-5000

In the environmental setting 1, specify the operation setting.
<>


During maintenance
During inhibit

Lamp on
Lamp off
Lamp blinking

2-5. SETTING1

Press SET key.

SE 0. INHIBIT

Set Inhibit.
Press the ▲ or ▼ key to select
either ON/OFF, and then press the
SET key to confirm the selection.
When ON is selected, the
character I is displayed on the
LCD. As a result, an alarm is not
triggered to external circuits even
though the indicator/alarm unit is
in the detection mode.

SE 1. ALM P

Set the alarm setpoint value.

Alarm setpoint value setting

=> P58

SE 2. ALM DLY

Set the alarm delay time.
Press the ▲ or ▼ key to
change the value (second),
and then press the SET key
to confirm the value.

SE 3. F TEST

Perform a fault alarm test.

Fault Alarm Test

=> P58

To SE 0.INHIBIT Setting