4 How to Use

4-3. Precautions for system designing

RM-5000

- 18 -

If load is to be activated, appropriate measures must be taken to stabilize the operation of the
indicator/alarm unit and protect the alarm contact referring to the following information.
• Relay it with an external relay at a lower voltage of 100 VAC or below (contact amplification). At the same

time, the surge absorbing part SK1 suitable for the specifications must be attached to the external relay.

• In addition, the surge absorbing part SK2 must be attached to the loaded side of the external relay if

necessary.

• It may be recommended that the surge absorbing part should be attached to the contact for certain load

conditions. It must be attached to an appropriate position by checking how the load is activated.


RM-5000

Load

SK1

SK2

Coil

Power

supply

Power

supply

Alarm contact

External relay

(low voltage relay)

* SK1, SK2: Surge absorbing parts