5. how to wire, Recommended cables, Caution – RKI Instruments RM-5000 Series Indicator/Alarm Unit User Manual
Page 21
4 How to Use
4-5. How to wire
- 21 -
RM-5000
4-5. How to wire
Model Cable
specifications
GP-5001
NC-5001
NC-5001W
SP-5001
Power supply: Equivalent to CVV (1.25 sq or 2.0 sq) - 2-core
Detector head: Equivalent to CVV (1.25 sq or 2.0 sq) - 4-core or 6-core
Signal:
Equivalent to CVVS (1.25 sq or 2.0 sq) - 2-core
Contact:
Equivalent to CVV (1.25 sq or 2.0 sq) - max. 6-core
NP-5001
Power supply: Equivalent to CVV (1.25 sq or 2.0 sq) - 2-core
Detector head: Equivalent to CVVS (1.25 sq or 2.0 sq) - 4-core or 6-core
Signal:
Equivalent to CVVS (1.25 sq or 2.0 sq) - 2-core
Contact:
Equivalent to CVV (1.25 sq or 2.0 sq) - max. 6-core
OX-5001
OX-5002
RM-5002
Power supply: Equivalent to CVV (1.25 sq or 2.0 sq) - 2-core
Detector head: Equivalent to CVVS (1.25 sq or 2.0 sq) - 2-core
Signal:
Equivalent to CVVS (1.25 sq or 2.0 sq) - 2-core
Contact:
Equivalent to CVV (1.25 sq or 2.0 sq) - max. 6-core
GH-5001
Power supply: Equivalent to CVV (1.25 sq or 2.0 sq) - 2-core
Detector head: Equivalent to CVVS (1.25 sq or 2.0 sq) - 3-core or 5-core
Signal:
Equivalent to CVVS (1.25 sq or 2.0 sq) - 2-core
Contact:
Equivalent to CVV (1.25 sq or 2.0 sq) - max. 6-core
EC-5002
Power supply: Equivalent to CVV (1.25 sq or 2.0 sq) - 2-core
Detector head: Equivalent to CVVS (1.25 sq or 2.0 sq) - 2-core or 4-core
Signal:
Equivalent to CVVS (1.25 sq or 2.0 sq) - 2-core
Contact:
Equivalent to CVV (1.25 sq or 2.0 sq) - max. 6-core
RM-5003
Power supply: Equivalent to CVV (1.25 sq or 2.0 sq) - 2-core
Detector head: Equivalent to CVVS (1.25 sq or 2.0 sq) - 3-core
Signal:
Equivalent to CVVS (1.25 sq or 2.0 sq) - 2-core
Contact:
Equivalent to CVV (1.25 sq or 2.0 sq) - max. 6-core
CAUTION
• Use the specified cables for each of the connections between the indicator/alarm unit and the
detector head.
• When wiring, be careful not to apply stresses on the terminal plate when (overweight) cables are
installed.
• The power cables and signal cables must not be installed together with the motor power cables,
etc.
• When stranded wires are used, prevent wires from contacting each other.
• Use the specified tools to wire.