3. external output operation – RKI Instruments GD-70D Series User Manual
Page 38

4 Detection Mode
4-3. External output operation
GD-70D
- 38 -
4-3. External output operation
Specifications
4 - 20 mA
Power-line communication system (NT)
Signal Transmission System
Electric current transmission (non-isolated)
2-wire type DC power-line communication
system
Transmission Path
CVVS
KPEV-S
Transmission Distance
Below 1 km
Below 300 m (depending on the system
designing conditions)
Connection Load Resistance
Below 300 Ω -
c
Detection Mode (No Alarm)
4 - 20 mA (concentration output)
Concentration data
d
Detection Mode (Gas Alarm)
4 - 20 mA (concentration output)
Concentration data, Alarm bits
e
Initial Clear
Depending on the setting of
f
2.5 mA setting: 2.5 mA
4 mA, HOLD, 4-20 mA setting: 4 mA*
Initial bit
f
Maintenance Mode
2.5 mA setting: 2.5 mA
4 mA setting: 4mA*
HOLD Setting: the previous value retained
4-20 mA setting: 4 - 20 mA (concentration output)
Concentration data, Adjustment bit
g
Alarm Test
Output ON setting: 4 - 20 mA (concentration output)
Output OFF setting: In accordance with setting of
f
Concentration data, Adjustment bit, Test bit
h
Fault Alarm
0.5 mA (Fixed)
Fault bits
i
Inhibit
Depending on the setting of
f
2.5 mA setting: 2.5 mA
4 mA, HOLD, 4 - 20 mA setting: 4 mA*
Concentration data, Adjustment bit, Inhibit bit
j
Power Off
0 mA
Signal OFF
* OSU - 0 - 25 vol% is equivalent of AIR (20.9 vol% = 17.4 mA)