2 Installation
2-3. How to wire
GD-70D
- 24 -
Connection conditions
• Cable: 0.08 - 2.5mm
2
• Bare wire length: 8 - 9 mm
• Connecting tool: Dedicated handling lever (accessory)
Compatible bar terminal
For a bar terminal, the following items are available.
• Bar terminal (ferrule): Model 216 Series (manufactured by WAGO)
• Crimping tool: Model VarioCrimp 4 (206-204) (manufactured by WAGO)
Dedicated
handling lever
CAUTION
• The specified bare wire length must be observed when the wire insulation is peeled off.
• Improper clamping of the wire due to a shorter bare wire length may cause defective electrification or
heating.
• Damaging the wire insulation due to a shorter bare wire length may cause defective electrification or
heating.
• Exposing the wire due to a longer bare wire length may cause defective insulation or a short circuit.
• Be careful not to break up the wire. If the wire is broken up when inserted to the terminal, this may
cause defective insulation or heating.
8 – 9 mm
CAUTION
• A bar terminal of the specified model must be used. Using other bar terminals invalidates the
guarantee of the performance.