DCA20SPXU2D 60 HZ GENERATOR • OPERATION AND PARTS MANUAL — REV. #1 (03/25/11) — PAGE 31

STARTING (AUTO MODE)

DANGER

Before connecting this generator to any
building’s electrical system, a licensed
electrician
must install an isolation
(transfer) switch.
Serious damage to
the building’s electrical system may occur

without this transfer switch.

CAUTION

When connecting the generator to a isolation (transfer)
switch, ALWAYS have power applied to the generator’s
internal battery charger. This will ensure that the engine
will not fail due to a dead battery.

WARNING

When running the generator in the AUTO mode,
remember the generator can start up at any time without
warning. NEVER attempt to perform any maintenance
when the generator is in the auto mode.

NOTICE

When the generator is placed in the AUTO mode, the
engine glow plugs will be warmed and the engine will
start automatically.

1. Pressing

the

AUTO button (Figure 30) on the controller

places the Digital Controller in the auto mode. This
mode allows the controller to monitor the remote start
contacts.

Closure of the remote start contacts will begin engine
cranking. When the contacts are opened, cranking will
stop or if the engine is running, engine will stop.

Figure 30. Auto Button

AUTO

NOTICE

If the generator is to be connected to a building's
AC power source via an automatic transfer switch
(isolation). Press the AUTO button (Figure 30).

In this position, should an outage occur, the automatic
transfer switch (ATS) will start the generator automatically
via the generator's auto-start contacts connected to the
ATS's start contacts.

Please refer to your ATS installation manual for further
instructions for the correct installation of the auto-start
contacts of the generator to the ATS.

NOTICE

When the generator is set in the AUTO mode, the
generator will automatically start in the event of
commercial power falling below a prescribed level
by means of a contact closure that is generated
automatically by a transfer switch.

GENERATOR START-UP PROCEDURE (AUTO)