INSPECTION/SETUP
CIRCUIT BREAKERS
To protect the generator from an overload, a 3-pole, 90 
amp, main circuit breaker is provided to protect the U,O 
and V Output Terminals from overload. In addition two 
single-pole, 20 amp GFCI circuit breakers are provided to 
protect the GFCI receptacles from overload. Two 50 amp 
load circuit breakers have also been provided to protect the 
auxiliary receptacles from overload. Make sure to switch 
ALL circuit breakers to the OFF position prior to starting 
the engine.
LUBRICATION OIL
Fill the engine crankcase with lubricating oil through the 
fi ller hole, but DO NOT overfi ll. Make sure the generator is 
level and verify that the oil level is maintained between the 
two notches (Figure 17) on the dipstick. See Table 8 for 
proper selection of engine oil.
Figure 17. Engine Oil Dipstick
When checking the engine oil, be sure to check if the oil is 
clean. If the oil is not clean, drain the oil by removing the 
oil drain plug, and refi ll with the specifi ed amount of oil as 
outlined in the ISUZU Engine Owner’s Manual. Oil should 
be warm before draining.
Other types of motor oils may be substituted if they meet 
the following requirements:
 API Service Classifi cation CC/SC
 API Service Classifi cation CC/SD
 API Service Classifi cation CC/SE
 API Service Classifi cation CC/SF
Table 8. Recommended Motor Oil
FUEL CHECK
Refi lling the Fuel System
This generator has an internal fuel tank located inside 
the trailer frame and may also be equipped with an 
environmental fuel tank (Figure 18). ALWAYS fi ll the fuel 
tanks with clean fresh #2 diesel fuel. DO NOT fi ll the fuel 
tanks beyond their capacities.
Pay attention to the fuel tank capacity when replenishing 
fuel. The fuel tank cap must be closed tightly after fi lling. 
Handle fuel in a safety container. If the container does not 
have a spout, use a funnel. Wipe up any spilled fuel 
immediately.
Figure 18. Internal Fuel Tank System
DANGER
Fuel spillage on a hot engine can cause 
a fi re or explosion. If fuel spillage occurs, 
wipe up the spilled fuel completely to 
prevent fire hazards. NEVER smoke 
around or near the generator.
CAUTION
ONLY properly trained personnel who have read 
and understand this section should refi ll the fuel tank 
system.