Impower series, Standing seam roof panel – Metal Sales IMPower Series User Manual

Page 13

background image

© Metal Sales Manufacturing Corporation / Subject to change without notice 1/14

12

IMPower Series

TM

STANDING SEAM ROOF PANEL

Interior Side

Exterior Side

3'-4"

SR2 STANDING SEAM ROOF SYSTEM

Panel Thickness 3.25"

4"

5"

6"

Insulating R-Values

26

32

41

49

Female Leg

Male Leg

S

tructural

l

oad

t

able

- t

hree

or

M

ore

S

panS

p

anel

t

hickneSS

p

anel

W

eight

d

eSign

c

riteria

S

pan

(

ft

.)

2.5

3

3.5

4

4.5

5

5.5

6

7

3.25"

2.48

Panel/Deflection Limit

149

123

104

90

79

70

62

56

46

4"

2.65

Panel/Deflection Limit

185

153

130

112

98

87

78

71

59

5"

2.86

Panel/Deflection Limit

233

192

164

142

125

111

100

90

75

6"

3.12

Panel/Deflection Limit

262

233

198

172

151

135

121

110

92

f

aStening

p

attern

c

onnection

S

trength

S

pan

(

ft

.)

2.5

3

3.5

4

4.5

5

5.5

6

7

(2) Fasteners

per Clip

16 gauge purlins

70

59

50

44

39

35

32

29

25

12 gauge purlins

149

124

106

93

83

75

68

62

53

3/16" thick purlins

294

247

213

186

165

148

136

124

106

(3) Fasteners

per Clip

16 gauge purlins

105

88

76

66

59

53

48

44

38

12 gauge purlins

223

186

160

140

124

112

102

93

80

NOTES:

1. Spans shown are based on transverse load testing per ASTM E 72 and strength of fastening patterns.
2. Spans calculated with 26 gauge exterior and interior facings.
3. The lowest allowable load between panel design and connection strength must be used to determine maximum span.
4. Fastening calculated with 1/4-14 Tek 3 for 16 gauge and 12 gauge purlins. 1/4-20 Tek 5 for 3/16" thick purlins.
5. Deflection limit: L/240
6. Safety Factor = 2.5 for buckling, 3.0 for shear, 3.0 for fastening.
7. Structural capacity of purlins have not been considered.
8. Thermal effect due to temperature differentials have not been considered.