3 module error messages, Module error messages, Safety option 30 – Lenze SO30 8400 protec User Manual
Page 59: Error management module error messages, 3 module error messages entries

Safety option 30
Error management
Module error messages
l
59
EDS84DPSO01 EN 2.1
5.8.3
Module error messages
Entries
Range
Description
Error type/response/
Note
Error number
Communication − standard device
16
0x10
Communication error − standard device
(communication between standard device and SM301 cancelled)
Warning/STO
17
0x11
Synchronisation error − standard device
No error status
Logbook entry/info
PROFIsafe
34
0x22
PROFIsafe communication error
PROFIsafe passivated/−
No error status
No diagnostic telegram via
PROFINET
35
0x23
F_WD_Time exceeded
(PROFIsafe monitoring time activated)
36
0x24
PROFIsafe deactivated
37
0x25
PROFIsafe has quit Data Exchange
38
0x26
PROFIsafe invalid data
39
0x27
Error − F parameter
(Wrong parameter setting of the F PLC)
PROFIsafe parameter
setting/STO
No error status
Inputs
49
0x31
Error − discrepancy or functional test SD−In1
Trouble/−
OFF state for the affected
input
50
0x32
Error − discrepancy or functional test SD−In2
53
0x35
Internal error AIS
54
0x36
Internal error AIE
55
0x37
Internal error − module switch
57
0x39
Deactivated SD−In1 = high
(Initialisation error, input in ON state)
Trouble/STO
58
0x3A
Deactivated SD−In2 = high
PROFIsafe
64
0x40
F_Dest_Add does not equal F address
PROFIsafe parameter
setting/STO
No error status
65
0x41
F_Dest_Add = 0 or FFFFhex
66
0x42
F_Source_Add = 0 or FFFFhex
67
0x43
F_WD_Time is 0 msec
68
0x44
F_SIL exceeds technical SIL
69
0x45
F_CRC_Length error
70
0x46
F parameter version incorrect
71
0x47
PROFIsafe CRC1 error
72
0x48
reserved (PS standard)
−
73
0x49
reserved (PS standard)
−
74
0x4A
reserved (PS standard)
−
Test functions
81
0x51
Error SD−Inx/CLx
(internal short circuit in one of the inputs)
Trouble/−
OFF state for all SD−In
93 0x5D
Error − internal disconnecting path
(internal error of the safe switch−off logic)
Trouble/STO
OFF state for all SD−In
94
0x5E
Test pulse error − internal switch−off path
(internal error of the safe switch−off logic)
Trouble/STO
Safety functions
97
0x61
SS1: Stopping time exceeded
(The drive has not reached zero speed within the stopping time.)
Warning/STO