3 safety option 10, 1 operating mode, 1 introduction – Lenze SO30 8400 protec User Manual
Page 14: 2 disconnecting paths, Safety option 10, Operating mode, Introduction, Disconnecting paths, 3safety option 10, Danger

Safety option 10
Operating mode
Introduction
3
l
14
EDS84DPSO01 EN 2.1
3
Safety option 10
3.1
Operating mode
3.1.1
Introduction
Due to safety option 10, the following safety functions can be used:
ƒ
Safe torque off (STO),
formerly: safe standstill
If requested, the safe disconnection of the drive is achieved through:
ƒ
Directly connected active sensors
ƒ
Passive sensors connected to a safety switching device
The safety functions are suitable for applications according to IEC 61508 to SIL 3 and
achieve a performance level (PL) e and the control category 4 according to EN ISO 13849−1.
}
Danger!
If the request for the safety function is cancelled, the drive will restart
automatically.
You must provide external measures which ensure that the drive only restarts
after a confirmation (EN 60204).
3.1.2
Disconnecting paths
The transmission of the pulse width modulation is safely switched (off) by the safety unit.
After this, the power drivers do not generate a rotating field. The motor is safely switched
to torqueless operation (STO).
M
SO
PWM
µC
P
C
3x
3x
Xxx
E84DPSO02
Fig. 3−1
Operating principle of safety unit
SO
Safety option 10, 20, or 30
xxx
Control terminals used in safety engineering systems or safety bus
C
Control section
mC
Microcontroller
PWM
Pulse width modulation
P
Power section
M
Motor