9 response times, Response times, Safety option 20 – Lenze SO30 8400 protec User Manual
Page 32: Μc s sf
Safety option 20
Response times
l
32
EDS84DPSO01 EN 2.1
4.9
Response times
In order to detect the response time to a safety function the entire system must be
considered. The following is relevant:
ƒ
Response time of the connected sensors.
ƒ
Input delay of the safety inputs.
ƒ
Internal processing time.
ƒ
When using PROFIsafe as safety bus:
– Monitoring time for the cyclic service in the PROFIBUS/PROFINET.
– Monitoring time of the PROFIsafe in the safety PLC.
– Processing time in the safety PLC.
ƒ
Delay times due to further components.
μC
μC
S
SF
t = 0
t
1
t
2
0
1
t
ps
t
4
2
3
t
3
t
5
t
i
lcu12x_352
Fig. 4−3
Response times to the request of a safety function
0 Standard device
1 Drive−based safety
2 Safety PLC
3 Safety bus
mC Microcontroller
S
Safety sensor technology
SF
Activated safety function