Limiting harmonic currents in the supply mains

16

l

EDBEMV EN 1.3

The listed measures ensure that inverters with DC voltage bus adhere to the limit values according
to EN 61000-3-2. The machine / system manufacturer is responsible for the compliance with the
regulations of the machine:

Connection voltage

Power

Measure

[V]

[kW]
0.25

Use assigned mains choke

1/N/PE AC 230 V

0.37

Use assigned mains choke

1/N/PE AC 230 V

0.55

Use active filter / PFC

0.75

Use active filter / PFC

3/PE AC 230 V

0.55

3/PE AC 230 V

0.75

Use assigned mains choke

3/PE AC 400V

0.55

Use assigned mains choke

3/PE AC 400V

0.75