Shielding

9

l

EDBEMV EN 1.3

5

Shielding

5.1

Shield connection

The quality of shielding is determined by:

z

a good shield connection

– a contact surface as large as possible

z

a low resistance:

– Only use shields with tin-plated or nickel-plated copper braids!

– Shields of steel braid are not suitable.

5.2

Shielding - what do you need to consider?

z

Always connect the shield to the conductive and grounded mounting plate with a surface as
large as possible via a conductive clamp.

z

Connect the shield directly to the corresponding device shield sheet.

z

Do not only connect the shield to the cable rail.

z

The unshielded cable ends must be as short as possible.

Short unshielded cable ends

Terminals must be separated, minimum distance: 100 mm

Minimum distance between the shield clamps for control cable and

motor cable: 50 mm

Fig. 5

Shielding for frequency inverters