3 motor cables, 4 control cables, Motor cables – Lenze Inverter EMC User Manual

Page 12: Control cables, Shielding, Cable gland

background image

Shielding

10

l

EDBEMV EN 1.3

5.3

Motor cables

z

If the motor cable must be interrupted by chokes or terminals, the unshielded cable must not
be longer than 40 - max. 100 m (depending on the cable cross-section).

z

If the motor cable must be interrupted by contactors, switches, or terminals, these must be
separated from the other components (with a min. distance of 100 mm).

z

In case of cable lengths up to 500 mm a second shield (shield connection) is not required.

Motor supply cable

max. 500mm

Large-surface

contact of

cable shield

Braid

Heat-shrinkable tube

Cable gland acc. to EMC with

high degree of protection

Cable gland

5.4

Control cables

z

The cables of the analog and digital inputs and outputs must be shielded. If short (up to 200
mm) and unshielded cables are used, they must be twisted.

z

In case of the analog cables the shield must only be connected to the controller.

z

In unfavorable conditions (very long cable, high interferences) it is possible in case of analog
cables to connect one shield end to PE via a capacitor (e.g. 10 nF/250 V) to have a better
shielding effect (see sketch).

z

In case of digital cables the shield must be connected on both sides.

z

The shields of the control cables must have a minimum distance of 50 mm to the shield
connections of the motor cables and DC cables.

Fig. 6

Shielding of long, analog control cables