3 motor cables, 4 control cables, Motor cables – Lenze Inverter EMC User Manual
Page 12: Control cables, Shielding, Cable gland

Shielding
10
l
EDBEMV EN 1.3
5.3
Motor cables
z
If the motor cable must be interrupted by chokes or terminals, the unshielded cable must not
be longer than 40 - max. 100 m (depending on the cable cross-section).
z
If the motor cable must be interrupted by contactors, switches, or terminals, these must be
separated from the other components (with a min. distance of 100 mm).
z
In case of cable lengths up to 500 mm a second shield (shield connection) is not required.
Motor supply cable
max. 500mm
Large-surface
contact of
cable shield
Braid
Heat-shrinkable tube
Cable gland acc. to EMC with
high degree of protection
Cable gland
5.4
Control cables
z
The cables of the analog and digital inputs and outputs must be shielded. If short (up to 200
mm) and unshielded cables are used, they must be twisted.
z
In case of the analog cables the shield must only be connected to the controller.
z
In unfavorable conditions (very long cable, high interferences) it is possible in case of analog
cables to connect one shield end to PE via a capacitor (e.g. 10 nF/250 V) to have a better
shielding effect (see sketch).
z
In case of digital cables the shield must be connected on both sides.
z
The shields of the control cables must have a minimum distance of 50 mm to the shield
connections of the motor cables and DC cables.
Fig. 6
Shielding of long, analog control cables