Codes 8 – Lenze E82ZAFVC010 User Manual
Page 47

Codes
l
47
EDS82ZAFVCxxx EN 4.0
C1512:
I/O data enable
Code
Subcode
Possible settings
Data type
Lenze
Selection
C1512 **
−
65535
0
[1]
65535
FIX32
If C1511 is changed, the process output data is automatically inhibited to ensure data
consistency.
Use the decimal value in code C1512 to enable some or all process output words (PAW)
again:
ƒ
0 = Inhibit PAW
ƒ
1 = Enable PAW
Bit 15 ... 12
Bit 11
Bit 10
...
Bit 1
Bit 0
reserved
PAW12
PAW 11
...
POW2
PAW 1
The bit settings 0 to 11 are each assigned to a process data word. The bit settings 12 to 15
are reserved.
Use the value 65535 (FFFF
hex
) in code C1512 to release all process output data.
)
Note!
ƒ
The release is required if the process output data configuration has been
changed.
C1516:
Baud rate setting
Code
Subcode
Possible settings
Data type
Lenze
Selection
C1516
0
see below
FIX32
Selection
Baud rate
0
125 kbits/s
1
250 kbits/s
2
500 kbits/s
255
Auto baud (automatic baud rate recognition)
Only valid if switches S7 and S8 are in the ON position.
)
Note!
Switch off the voltage supply of the function module and then on again to
activate changed settings of the baud rate.