Commissioning – Lenze E82ZAFVC010 User Manual
Page 32

Commissioning
Controls and displays
Possible settings using the front switch
l
32
EDS82ZAFVCxxx EN 4.0
Setting of the device address
)
Note!
The device address must be set via software, when the switches S7 and S8 are
in ON position.
In this case the switches S1 to S6 are ineffective.
ON
1
6
2
7
4
3
8
5
9 10
ON
OFF
Fig. 6−2
Address assignment via DIP switch
)
Note!
The addresses of all controllers connected to the network must differ from
each other.
The device address (decimal number) is calculated by inserting the positions of the
switches S1 ... S6 (’0’ = OFF and ’1’ = ON) into the following equation:
Address
dec
= S6 · 2
0
+ S5 · 2
1
+ S4 · 2
2
+ S3 · 2
3
+ S2 · 2
4
+ S1 · 2
5
The equation also allows you to calculate the valency of a confirmed switch. The sum of
valencies results in the device address to be set:
Switch
Valency
Example
Switch position
Address
S1
32
ON
32 + 16+ 8 = 56
S2
16
ON
S3
8
ON
S4
4
OFF
S5
2
OFF
S6
1
OFF