Installation – Lenze E82ZAFVC010 User Manual
Page 23

Installation
Electrical installation
Wiring with a host (master)
l
23
EDS82ZAFVCxxx EN 4.0
Features of the data line
Insulation diameter
1.96 mm (nom.)
Conductor pair
At least copper 24; at least 19 cores (individually tinned)
Colours
Light blue, white
Pair windings / m
Approx. 16
Shielding/conductor pair
1000/1000, Al/Mylar, Al side on the outside, with w/shorting fold (for tensile load)
Impedance
120
W +/− 10 % at 1 MHz
Runtime
4.46 ns/m (max.)
Capacitance between conductors
39.37 pF/m at 1 kHz (nom.)
Capacitance between one conductor and another which is
connected to the shield.
78.74 pF/m at 1 kHz (nom.)
Capacitive assymetry
3.94 pF/km at 1 kHz (max.)
Spec. DC resistance at 20 °C
91.86
W/km (max.)
Damping
0.95 dB/100 m at 125 kHz (max.)
1.64 dB/100 m at 500 kHz (max.)
2.30 dB/100 m at 1.00 MHz (max.)
Features of the voltage line
Conductor pair
At least copper 22; at least 19 cores (individually tinned)
Insulation diameter
1.4 mm (nominal)
Colours
Red, black
Pair windings / m
Approx. 16
Shielding/conductor pair
1000/1000, Al/Mylar, Al side on the outside, with w/shorting fold (for tensile load)
Spec. DC resistance at 20 °C
57.41