7 diagnostics, 1 led status displays, Diagnostics – Lenze E82ZAFVC010 User Manual
Page 34: Led status displays, 7diagnostics

Diagnostics
LED status displays
7
l
34
EDS82ZAFVCxxx EN 4.0
7
Diagnostics
7.1
LED status displays
Function module E82ZAFVC001
Function module E82ZAFVC010
E82ZAFD001A*
E82ZAFD101A*
Pos
Colour
Status
Notes
1
off
Function module is not supplied with voltage,
external voltage supply is switched off
green
blinking
Function module is supplied with voltage but not connected to the controller.
Reason:
Standard device is
l
switched off
l
is being initialised
l
not available
on
Function module is supplied with voltage and is connected to the standard
device
red
blinking
Internal error, Lenze setting has been loaded
on
Internal error of the function module
2
off
l
No connection to the master
l
Function module is not supplied with voltage.
green
blinking
Dup_Mac_ID" test phase. Not yet connected to master (scanner).
on
DeviceNet connection established.
red
blinking
No communication due to time−out
on
Critical bus error