3 protective insulation, Protective insulation, External measures. (see chapter "4.3 – Lenze E82ZAFVC010 User Manual
Page 16: Technical data, Danger

Technical data
Protective insulation
l
16
EDS82ZAFVCxxx EN 4.0
4.3
Protective insulation
{
Danger!
Dangerous electrical voltage
If Lenze controllers are used on a phase earthed mains with a rated mains
voltage
³ 400 V, protection against accidental contact is not ensured without
implementing external measures.
Possible consequences:
ƒ
Death or serious injury
Protective measures:
ƒ
If protection against accidental contact is required for the control terminals
of the controller and the connections of the plugged device modules, ...
– a double isolating distance must exist.
– the components to be connected must be provided with the second
isolating distance.
E82ZAFVC001
function module
Protective insulation between bus and ...
Type of insulation (acc. to EN 61800−5−1)
l
reference earth / PE (X3/SH)
Functional insulation
l
external supply (X3/V+)
No electrical isolation
l
supply for CINH (X3/20)
No electrical isolation
l
controller inhibit, CINH (X3/28)
Functional insulation
l
power section
– 8200 vector
Reinforced insulation
– 8200 motec
Reinforced insulation
– starttec
Reinforced insulation
l
control terminals
– 8200 vector
Functional insulation
– 8200 motec
Functional insulation
E82ZAFVC010
function module
Protective insulation between bus and ...
Type of insulation
l
Reference earth / PE (X3.1/SH)
Functional insulation
l
External supply (X3.1/V+)
No functional insulation
l
Supply for CINH (X3.2/20)
No functional insulation
l
Controller inhibit, CINH (X3.2/28)
Functional insulation
l
8200 vectorpower unit
Double insulation
l
8200 vector control terminals
Functional insulation