Parameter data transfer – Lenze EMF2192IB User Manual
Page 51

Parameter data transfer
Reading and writing parameters
Writing parameters (expedited download)
l
51
EDSMF2192IB EN 3.1
Example
The transmitted request structure in case of a download from the index 0x1600 contains
the following data:
SDO frame
area
Data field
Data type / length
Value [hex] / description
Mailbox Header
Length
WORD
2 bytes
0xA: Length of the mailbox service data
Address
WORD
2 bytes
0x0
Channel
WORD
6 bits (0 ... 5)
0x0: Reserved
Priority
2 bits (6, 7)
0x0: Lowest priority
Type
4 bits (8 ... 11)
0x3: CANopen over EtherCAT (CoE)
Reserved
4 bits (12 ... 15)
0x0
CANopen Header
Number
WORD
9 bits (0 ...8)
0x0
Reserved
3 bits (9... 11)
0x0
Service
4 bits (12 ... 15)
0x2: SDO request
SDO
Size indicator
BYTE
1 bit (0)
0x01: Size of the data in "data set size"
Transfer type
1 bit (1)
0x01: Expedited transfer
Data set size
2 bits (2, 3)
0x00: 4 bytes data
Complete access
1 bit (4)
0x00: The entry addressed with index and subindex is written.
Command specifier
3 bits (5 ... 7)
0x01: Download Request
Index
WORD
2 bytes
0x00: Index low byte of the object
0x16: Index high byte of the object
Subindex
BYTE
1 byte
0x01: Subindex of the object
Data
DWORD
4 bytes
0x5C930110