1 reading parameters (expedited upload), Reading parameters (expedited upload), Parameter data transfer – Lenze EMF2192IB User Manual
Page 44

Parameter data transfer
Reading and writing parameters
Reading parameters (expedited upload)
l
44
EDSMF2192IB EN 3.1
9.2.1
Reading parameters (expedited upload)
1. The master transmits "Initiate Domain Upload Request".
2. The slave acknowledges the request with a positive response ("Initiate Domain
Upload Response").
In the event of an error the slave responds with "Abort Domain Transfer".
)
Note!
In the case of jobs for the controller, please make sure that you convert the
code into an index (
¶ 43).
SDO Upload Request
Detailed breakdown of the data for an "SDO Upload Request":
SDO frame
area
Data field
Data type / length
Value / description
Mailbox Header
Length
WORD
2 bytes
0x0: Length of the mailbox service data
Address
WORD
2 bytes
Station address of the source if an EtherCAT master is the instructing
party.
Station address of the target if an EtherCAT slave is the instructing
party.
Channel
WORD
6 bits (0 ... 5)
0x00: Reserved
Priority
2 bits (6, 7)
0x00: Lowest priority
...
0x03: Highest priority
Type
4 bits (8 ... 11)
0x03: CANopen over EtherCAT (CoE)
Reserved
4 bits (12 ... 15)
0x00
CANopen Header
Number
WORD
9 bits (0 ... 8)
0x00
Reserved
3 bits (9 ... 11)
0x00
Service
4 bits (12 ... 15)
0x02: SDO Request
SDO
Reserved
BYTE
4 bits (0 ... 3)
0x00
Complete access
1 bit (4)
0x00: The entry addressed with index and subindex is read.
0x01: The complete object is read.
Command specifier
3 bits (5 ... 7)
0x02: Upload Request
Index
WORD
2 bytes
Index of the object
Subindex
BYTE
1 byte
Subindex of the object
0x00 or 0x01 if "complete access" = 0x01.
Reserved
DWORD
4 bytes
0x00