C13880 | reaction on communication failure, C13881 | monit. time: data exchange, C13880 – Lenze E84Dxxxx User Manual
Page 83: Is executed in the controller, For the "data_exchange" status, C13881, Is set, Lenze setting: "no response"), C13880/1, C13880/2

Communication manual 8400 protec PROFIBUS
Parameter reference
Parameters relevant for the communication
83
L
EDS84DPBUS EN 2.0 - 09/2010
C13880
C13881
Parameter | Name:
C13880 | Reaction on communication failure
Data type: UNSIGNED_8
Index: 10695
d
= 29C7
h
Monitoring response in case of a communication fault on the PROFIBUS
• A change of the monitoring response is effective immediately.
Permanent interruption of PROFIBUS communication ( 64)
Selection list
0 No response
1 Fault
3 Quick stop by trouble
4 Warning locked
6 Information
Subcodes
Lenze setting
Info
C13880/1
0: No response
The response set here for the "watchdog/data exchange"
monitoring is executed if the bus station ...
• does not receive a message from the master within
the watchdog monitoring time (during an active
connection displayed under
).
• detects that it is no longer in the "DATA_EXCHANGE"
status. Please see also the notes given under
C13880/2
0: No response
The response set here for "DPV1 MSC2" monitoring is
activated if, during the monitoring time (during an active
connection displayed in
), the node does not
receive a "DPV1 MSAC2" message from the master and
the MSAC2 connection is stopped from the slave.
Note:We recommend to set "Information" for the
response in order that no drive-relevant response takes
place.
;
Read access ; Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13881 | Monit. time: Data exchange
Data type: UNSIGNED_16
Index: 10694
d
= 29C6
h
If the DATA_EXCHANGE state has been exited, the response parameterised with
is carried out when the
time set here for the data exchange has expired.
• The value "65535" in this code deactivates monitoring.
• A change in monitoring is effective immediately.
• The value set here for the monitoring time must be smaller than the watchdog monitoring time (displayed under
Permanent interruption of PROFIBUS communication ( 64)
Setting range
(min. value | unit | max. value)
Lenze setting
0
ms
65535 65535 ms
;
Read access ; Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT