C13864 | active station address, C13865 | display: last prm data, C13866 | display: last cfg data – Lenze E84Dxxxx User Manual
Page 82: C13867 | display: last diagnostic data, C13864, Communication manual 8400 protec profibus

EDS84DPBUS EN 2.0 - 09/2010
L
82
Communication manual 8400 protec PROFIBUS
Parameter reference
Parameters relevant for the communication
C13864
C13865
C13866
C13867
Parameter | Name:
C13864 | Active station address
Data type: UNSIGNED_8
Index: 10711
d
= 29D7
h
Display of active station address
• If the front panel DIP switches 1 to 64 are all in the "OFF" position (Lenze setting), the station address
parameterised under
becomes active and is displayed here after switching on.
Setting the station address ( 24)
Display area
(min. value | unit | max. value)
0
255
;
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13865 | Display: Last PRM data
Data type: OCTET_STRING
Index: 10710
d
= 29D6
h
Display of the most recently sent parameter data from the PROFIBUS master with the "Set-Prm" telegram (ASCII
string with 24 digits)
;
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13866 | Display: Last CFG data
Data type: OCTET_STRING
Index: 10709
d
= 29D5
h
Display of the most recently sent configuration data from the PROFIBUS master with the "Chk-Cfg" telegram (ASCII
string with 22 digits)
;
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13867 | Display: Last diagnostic data
Data type: OCTET_STRING
Index: 10708
d
= 29D4
h
Display of the most recently sent diagnostic data to the PROFIBUS master (ASCII string with 16 digits)
Advanced diagnostic message ( 71)
;
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT