Safety instructions
Residual hazards
l
52
EDK94AMH24 DE/EN/FR/ES/IT 3.1
2.2
Residual hazards
Protection of persons
ƒ
Before starting work on the controller, check that the power terminals are
deenergised
– because the power terminals U, V, W, +UG and −UG carry hazardous voltages for at
least 3 minutes after mains disconnection.
– because the power terminals U, V, W, +UG and −UG carry hazardous voltages when
the motor is stopped.
Device protection
ƒ
Plug on or pull off all pluggable terminals only in deenergised condition!
ƒ
Detach the controllers only in deenergised conditions from their installation
backplanes or the back panel of the control cabinet!
ƒ
Cyclic switching on and off of the mains voltage can overload and destroy the input
current limitation of the controller:
– Cyclic mains switching of 5−times in 5 minutes is permissible without restrictions.
Motor protection
ƒ
Depending on the controller settings, the connected motor can be overheated by:
– For instance, longer DC−braking operations.
– Longer operation of self−ventilated motors at low speed.
Protection of the machine/system
ƒ
Drives can reach dangerous overspeeds (e.g. setting of high output frequencies in
connection with motors and machines unsuitable for such conditions):
– The controllers do not offer any protection against such operating conditions. Use
additional components for this purpose.