beautypg.com

Technical data – JUMO 902931 Wtrans Receiver with Wireless Data Transmission Data Sheet User Manual

Page 2

background image

JUMO GmbH & Co. KG
Delivery address: Mackenrodtstraße 14

36039 Fulda, Germany

Postal address:

36035 Fulda, Germany

Phone:

+49 661 6003-0

Fax:

+49 661 6003-607

E-mail:

[email protected]

Internet:

www.jumo.net

JUMO Instrument Co. Ltd.
JUMO House
Temple Bank, Riverway
Harlow, Essex CM20 2DY, UK
Phone: +44 1279 635533
Fax:

+44 1279 635262

E-mail:

[email protected]

Internet: www.jumo.co.uk

JUMO Process Control, Inc.
8 Technology Boulevard
Canastota, NY 13032, USA
Phone: 315-697-5866

1-800-554-JUMO

Fax:

315-697-5867

E-mail:

[email protected]

Internet: www.jumousa.com

2012-06-20/00473257

Data Sheet 902931

Page 2/10

Technical data

Input

Number of transmitters

Up to 16 transmitters can be received per receiver.

Radio frequency

868.4 MHz (Europe);
915 MHz (America, Australia, Canada, and New Zealand);
Ten frequencies can be configured in the 915 MHz frequency band.

Open air range

Up to 300 m when using the antenna wall holder with a 3 m antenna cable
When installing the antenna directly to the receiver, a reduced range of approx. 40 % must be
taken into account.

Measuring range limits

Depending on the set sensor

Configuration

Using the keys on the device or the setup program

Unit

The units for temperature, pressure, potentiometer, and voltage
are configurable on the device or with the setup program.

Analog outputs

Quantity

4 analog outputs for basic type 902931/10, 2 analog outputs for basic type 902931/30

Output signal:
- Current
- Voltage

Configurable with the keys on the device or the setup program
Load-independent direct current 0 to20 mA or 4 to 20 mA
Direct voltage 0 to 10 V

Transmission behavior

Linear, freely scalable

Burden (at current output)

500 ohm

Load (at voltage output)

10 k ohm

Setting time for temperature changes

The setting time depends on the transmission interval that is set in the transmitter.

Setting time after switch-on or reset

5 s

Calibration conditions

AC 230 V/22 °C (±3 K) or DC 24 V/22 °C (±3 K)

Accuracy

±0.1 %

1

(accuracy includes calibration, linearization, burden influence, load error,
and voltage supply error)

Residual ripple

±0.2 %

1

Electrical isolation

The analog outputs are electrically isolated from each other and the interfaces.

Isolation voltage

50 V

Measuring circuit monitoring of the analog outputs

Underrange
- Current output 4 to 20 mA
- Current output 0 to 20 mA
- Voltage output 0 to 10 V

Dropping to 3.8 mA, then jump to the configured signaling
Dropping to -0.1 mA, then jump to the configured signaling
Dropping to -0.1 V, then jump to the configured signaling

Overrange
- Current output 4 to 20 mA
- Current output 0 to 20 mA
- Voltage output 0 to 10 V

Increasing to 20.5 mA, then jump to the configured signaling
Increasing to 20.5 mA, then jump to the configured signaling
Increasing to 10.25 V, then jump to the configured signaling

Probe short-circuit or
Probe/cable break and alarms:
- Current output 4 to 20 mA

- Current output 0 to 20 mA

- Voltage output 0 to 10 V

Positive signaling: > 21 mA
Negative signaling: < 3.6 mA
Positive signaling: > 21 mA
Negative signaling: < -0.1 mA
Positive signaling: > 10.5 V
Negative signaling: < -0.1 V

Output behavior

The output behavior (positive or negative signaling) can be configured.

1

All accuracy specifications in % from the measuring range end value of 20 mA or 10 V.