Connection diagram
The connection diagram in the data sheet provides preliminary information about the connection possibilities. For the electrical connec-
tion only use the installation instructions or the operating manual. The knowledge and the correct technical execution of the safety in-
formation/instructions contained in these documents are mandatory for installation, electrical connection, and startup as well as for
safety during operation.
The connection is made via screw terminals.
Lead
Admissible cross
section
1-wire
≤
2.5 mm
2
Fine-strand,
with ferrule
≤
1.5 mm
2
Tightening torque of the screws:
max. 0.5 Nm
Legend:
Comment
Screw terminals
Screw terminals
1, 2
Analog input 1 (E1)
Analog input 2 (E2)
Thermocouple /
Double thermocouple
RTD temperature probe in 2-wire circuit
RTD temperature probe Pt100/Pt1000 in 3-wire cir-
cuit
RTD temperature probe Pt100 in
2-wire circuit, single sensor for both analog inputs
Caution:
When only one probe (SIL2) is connected, the temperature limiter device is reduced from SIL3 to SIL2! However, the internal 2-channel structure
(1oo2D) in the device still remains. Both channels measure the same sensor due to the simplified external wiring.
(4) to 20 mA
(4) to 20 mA for both analog inputs
Caution:
When only one probe (SIL2) is connected, the temperature limiter device is reduced from SIL3 to SIL2! However, the internal 2-channel structure
(1oo2D) in the device still remains. Both channels measure the same current signal due to the simplified external wiring.
+
–
2
3
+
–
7
8
J
1
3
J
6
8
A
Enter the lead wire resistance for RTD temperature probes in 2-wire circuit when using greater line lengths.
Setup program: edit => analog inputs
1
2
3
J
6
7
8
J
J
1
3
6
8
2
3
+
–
I
x
7
8
+
–
I
x
2
+
–
I
x
7
Caution:
The protection cover must be removed
prior to wiring and put back on when
finished.
This is necessary for the proper opera-
tion of the probe in the Ex-area!