beautypg.com

Connection diagram – JUMO 14597 safetyM STB/STW Ex - Safety Temperature Limiter and Safety Temperature Monitor Data Sheet User Manual

Page 7

background image

2012-10-01/00542385

Data Sheet 701155

Page 7/16

JUMO GmbH & Co. KG
Delivery address: Mackenrodtstraße 14

36039 Fulda, Germany

Postal address:

36035 Fulda, Germany

Phone:

+49 661 6003-0

Fax:

+49 661 6003-607

E-mail:

[email protected]

Internet:

www.jumo.net

JUMO Instrument Co. Ltd.
JUMO House
Temple Bank, Riverway
Harlow, Essex CM20 2DY, UK
Phone: +44 1279 635533
Fax:

+44 1279 635262

E-mail:

[email protected]

Internet: www.jumo.co.uk

JUMO Process Control, Inc.
6733 Myers Road
East Syracuse, NY 13057, USA
Phone: 315-437-5866

1-800-554-5866

Fax:

315-437-5860

E-mail:

[email protected]

Internet: www.jumousa.com

Connection diagram

The connection diagram in the data sheet provides preliminary information about the connection possibilities. For the electrical connec-
tion only use the installation instructions or the operating manual. The knowledge and the correct technical execution of the safety in-
formation/instructions contained in these documents are mandatory for installation, electrical connection, and startup as well as for
safety during operation.

The connection is made via screw terminals.

Lead

Admissible cross
section

1-wire

2.5 mm

2

Fine-strand,
with ferrule

1.5 mm

2

Tightening torque of the screws:
max. 0.5 Nm

Legend:

Comment

Screw terminals

Screw terminals

1, 2

Analog input 1 (E1)

Analog input 2 (E2)

Thermocouple /
Double thermocouple

RTD temperature probe in 2-wire circuit

RTD temperature probe Pt100/Pt1000 in 3-wire cir-
cuit

RTD temperature probe Pt100 in
2-wire circuit, single sensor for both analog inputs

Caution:
When only one probe (SIL2) is connected, the temperature limiter device is reduced from SIL3 to SIL2! However, the internal 2-channel structure
(1oo2D) in the device still remains. Both channels measure the same sensor due to the simplified external wiring.

(4) to 20 mA

(4) to 20 mA for both analog inputs

Caution:
When only one probe (SIL2) is connected, the temperature limiter device is reduced from SIL3 to SIL2! However, the internal 2-channel structure
(1oo2D) in the device still remains. Both channels measure the same current signal due to the simplified external wiring.

+

2

3

+

7

8

J

1

3

J

6

8

A

Enter the lead wire resistance for RTD temperature probes in 2-wire circuit when using greater line lengths.
Setup program: edit => analog inputs

1

2

3

J

6

7

8

J

J

1

3

6

8

2

3

+

I

x

7

8

+

I

x

2

+

I

x

7

Caution:
The protection cover must be removed
prior to wiring and put back on when
finished.
This is necessary for the proper opera-
tion of the probe in the Ex-area!