Technical data, Analog inputs, Analog output – JUMO 14597 safetyM STB/STW Ex - Safety Temperature Limiter and Safety Temperature Monitor Data Sheet User Manual

Page 2

background image

2012-10-01/00542385

Data Sheet 701155

Page 2/16

JUMO GmbH & Co. KG
Delivery address: Mackenrodtstraße 14

36039 Fulda, Germany

Postal address:

36035 Fulda, Germany

Phone:

+49 661 6003-0

Fax:

+49 661 6003-607

E-mail:

[email protected]

Internet:

www.jumo.net

JUMO Instrument Co. Ltd.
JUMO House
Temple Bank, Riverway
Harlow, Essex CM20 2DY, UK
Phone: +44 1279 635533
Fax:

+44 1279 635262

E-mail:

[email protected]

Internet: www.jumo.co.uk

JUMO Process Control, Inc.
6733 Myers Road
East Syracuse, NY 13057, USA
Phone: 315-437-5866

1-800-554-5866

Fax:

315-437-5860

E-mail:

[email protected]

Internet: www.jumousa.com

Technical data

Analog inputs

RTD temperature probe

Thermocouples

Direct current

Analog output

Designation Measuring range

Accuracy
2/3-wire circuit

1

Ambient temperature influence

Pt100 DIN EN 60751

-200 to +850 °C

0.5 % / 0.1 %

50 ppm/K

Pt1000 DIN EN 60751

-200 to +850 °C

0.5 % / 0.1 %

50 ppm/K

Connection type

2-wire, 3-wire circuit

Maximum output resistance 30

Ω

Measuring rate

210 ms

Error tolerance time

5 s: time taken into account for all diagnostic tests

Input filter

Digital filter, 2nd order; filter constant can be set from 0 to 100 s

Special features

Individual probe Pt100 2-wire,
display can also be programmed in °F

Designation Measuring range

Accuracy

1

Ambient temperature influence

Fe-CuNi "L" DIN 43710

-200 to +900 °C

0.4 %

100 ppm/K

Fe-CuNi "J" DIN EN 60584

-200 to +1200 °C

0.4 %

100 ppm/K

Cu-CuNi "U" DIN 43710

-200 to +600 °C

0.4 %

100 ppm/K

Cu-CuNi "T" DIN EN 60584

-200 to +400 °C

0.4 %

100 ppm/K

NiCr-Ni "K" DIN EN 60584

-200 to +1372 °C

0.4 %

100 ppm/K

NiCrSi-NiSi "N" DIN EN 60584

-100 to +1300 °C

0.4 %

100 ppm/K

Pt10Rh-Pt "S" DIN EN 60584

0 to +1768 °C

0.4 %

100 ppm/K

Pt13Rh-Pt "R" DIN EN 60584

0 to +1768 °C

0.4 %

100 ppm/K

Pt30Rh-Pt6Rh "B" DIN EN 60584

300 to 1820 °C

0.4 %

100 ppm/K

W3Re-W25Re "D"

0 to 2495 °C

0.4 %

100 ppm/K

Cold junction

Pt100 internal

Cold junction accuracy

±1 K

Sampling rate

210 ms

Error tolerance time

5 s: time taken into account for all diagnostic tests

Input filter

Digital filter, 2nd order; filter constant can be set from 0 to 100 s

1. The accuracy values refer to the maximum measuring range.

Measuring range

Accuracy

Ambient temperature influence

4 to 20mA, voltage drop < 2 V

0.2 %

150 ppm/K

Scaling

Can be freely programmed within the limits

Sampling rate

210 ms

Error tolerance time

5 s: time taken into account for all diagnostic tests

Input filter

Digital filter, 2nd order; filter constant can be set from 0 to 100 s

Special features

Individual probe 4 to 20 mA

Type of signal

Accuracy

Residual ripple

Load influence

Temperature influence

Load resistance

Current

4 to 20 mA

0.5 %

± 0.5 % at 300

Ω

± 0.05 mA / 100

Ω

150 ppm/K

500

Ω

0 to 20 mA

Voltage

2 to 10 V

0.5 %

± 0.5 %

± 15 mV

150 ppm/K

500

Ω

0 to 10 V