Valid range valid range, Allo, Alhi hys1 hys2 – JUMO 14597 safetyM TB/TW08 Temperature Limiter and Temperature Monitor Data Sheet User Manual

Page 4

background image

2012-07-01/00524703

Data sheet 70.1170

JUMO GmbH & Co. KG • 36035 Fulda, Germany

Page 4/10

Switching behavior, direct

Switching behavior with differential value calculation with prefix (ex-factory)

Pre alarm range

Alarm range

valid range

Relay output KV
LED KV lights up yellow

active

Relay output KV inaktive
LED KV off

ALLO

Relay inaktive
LED K1 lights up red

Relay K1 aktive

Limit Value

AL

Measured Value

LED OK

green

lights up

Pre alarm

ALHI

Hys1

Hys2

S

P

Ö

3,15A

5

7

6

S

P

5

7

6

Ö

3,15A

Measured Value

-200°C

300°C

AL = 150°C (inverse)

0°C

200°C

100°C

-100°C

300°C

200°C

100°C

0°C

-100°C

-200°C

ALD = 50°C

IN2

INP

valid

range

valid

range

Hys1

Hys1

All difference values diF = INP-IN2 are shown in the picture.
Inside the valid range (green) all values are smaller than the
setting for the difference ALd = 50.

INP = 101°C, IN2 = 50°C
101 - 50 = 51 exceeds Ald = 50 and lies out of the valid range.

INP = 50°C, IN2 = 50°C
50 - 50 = 0 and lies inside the valid range.

Example 1:

Example 2:

The area between the dot and dash lines indicate
the span of the hysteresis (factory setting: 1K)

he inputs INP and IN2 are additionally monitored

in regards to the limit value AL=150°C

T

50°C

1

2