Allo al alhi hys1 hys2 – JUMO 14597 safetyM TB/TW08 Temperature Limiter and Temperature Monitor Data Sheet User Manual
Page 3

2012-07-01/00524703
Data sheet 70.1170
JUMO GmbH & Co. KG • 36035 Fulda, Germany
Page 3/10
Analog output
Binary input
Relay outputs
Voltage supply
Approval/approval marks
Switching behavior inverse (ex-factory)
Type of signal Accuracy
Residual ripple
Load influence
Temperature coeffi-
cient
Load resistance
Current
4 ... 20 mA
≤
0.5 %
± 0.5 %
± 0.01 mA
80 ppm/K
≤
500
Ω
0 ... 20 mA
Voltage
2 ... 10 V
≤
0.5 %
± 0.5 %
± 15 mV
80 ppm/K
≥
500
Ω
0 ... 10 V
Connection
Function
1 potential-free contact
Unlocking, keyboard locking, level locking can be configured
Relay output KV
Relay (N/O) without shroud
Contact rating of 3A /230V, 50 Hz ohmic load
Relay output K1
100000 operations at a performance of 3A /230V, 50Hz resistive load
Contact protection switching:
Fuse cut-out 3,15AT installed in the device
Voltage supply
AC/DC 20 ... 30V, 48 ...63 Hz, AC 110 ... 240V +10% /-15%, 48 ... 63Hz
Power consumption
< 15 VA
Approval
marks
Inspection authority
Certificates/inspection
numbers
Inspection basics
valid for
DIN
DIN CERTCO
TW/TB 1219
DIN EN 14597
all device versions
c UL us
Underwriters Laboratories -
UL 60730-2-9
submitted
all device versions
ALLO
AL
ALHI
Hys1
Hys2
S
P
Ö
3,15A
5
7
6
S
P
5
7
6
Ö
3,15A
Relay output KV
LED KV lights up yellow
active
Relay output KV inaktive
LED KV off
Relay inaktive
LED K1 lights up red
Relay K1 aktive
LED OK
green
lights up
Pre alarm range
Pre alarm
Measured Value
Measured Value
Limit Value
Alarm range
Valid range