Technical data, Analog inputs, Measuring circuit monitoring – JUMO 14597 safetyM TB/TW08 Temperature Limiter and Temperature Monitor Data Sheet User Manual
Page 2

2012-07-01/00524703
Data sheet 70.1170
JUMO GmbH & Co. KG • 36035 Fulda, Germany
Page 2/10
Technical Data
Analog inputs
RTD temperature probe
Thermocouples
Direct current
Measuring circuit monitoring
Designation
Measuring range
Accuracy
1
Pt 100
DIN EN 60751
-200 … +850°C
0.1%
KTY11-6 PTC
-50 ... 150°C
1%
Pt 1000
DIN EN 60751
-200 … +850°C
0.1%
Connection type
2-wire, 3-wire circuit
Detection rate
210ms
Input filter
digital filter, 2st priority; filter constant can be set from 0 … 100s
Special features
2xPt100 for differential value calculation, display can also be programmed in °F
Designation
Measuring range
Accuracy
1
Fe-CuNi „L“
DIN 43710
-200 … +900°C
0.4%
Fe-CuNi „J“
DIN EN60584
-200 … +1200°C
0.4%
Cu-CuNi „U“
DIN 43710
-200 … +600°C
0.4%
Cu-CuNi „T“
DIN EN60584
-200 … +400°C
0.4%
NiCr-Ni „K“
DIN EN60584
-200 … +1372°C
0.4%
NiCrSi-NiSi „N“
DIN EN60584
-100 … +1300°C
0.4%
Pt10Rh-Pt „S“
DIN EN60584
0
… +1768°C
0.4%
Pt13Rh-Pt „R“
DIN EN60584
0
… +1768°C
0.4%
Pt30Rh-Pt6Rh „B“ DIN EN60584
300 … 1820°C
0.4%
W3Re-W25Re„D“
0
... 2495°C
0.4%
Cold junction
Pt 100 internal
Cold junction accuracy
± 1K
Detection rate
210 ms, 420ms with double thermocouples (C112=1)
Input filter
digital filter, 2st priority; filter constant can be set from 0 … 100s
Special features
can also be programmed in °F
1. The accuracy values refer to the maximum measuring range. Small measuring ranges lead to reduced linearization accuracy.
Measuring range
Accuracy
0 … 20mA, voltage drop < 2V
4 … 20mA, voltage drop < 2V
0.2%
0 … 10V, input resistance > 100 k
Ω
2 … 10V, input resistance > 100 k
Ω
0.1%
Scaling
can be freely programmed within the limits
Measuring range
210 ms
Input filter
digital filter, 2st priority; filter constant can be set from 0 … 100s
RTD temperature probe
and KTY11-6
Double thermocouples
Thermocouples
Current 0 ... 20 mA, 4 ... 20mA
Voltage 0 ... 10 V, 2 ... 10 V
Overrange
and underrange
is detected
LED K1 and KV are lit; "9999“ flashes in the display
Probe and
wire break
is detected
LED K1 and KV are lit; "9999“ flashes in the display;
relay output K1 is inactive
is detected at 4…20mA
and 2…10V
LED K1 and KV are lit;
"9999“ flashes in the display
Relay K1 is inactive
Probe short-circuit
is detected
LED K1 and KV are lit; "9999“ flashes in the display;
Relay output K1 is inactive
is not detected