6 Instrument description

Capillary
and
probe material

Min. bending
radius of
capillary

5 mm

Switching point
accuracy

in % of scale span, referred to limit at T

a

+22°C.

Mean ambient
temperature
effect

in % of scale span, referred to limit.

A deviation of the ambient temperature at the housing and / or the capillary
from the calibrated ambient temperature +22°C will result in a switching point
displacement:
higher ambient temperature = lower switching point
lower ambient temperature = higher switching point

End of scale

Capillary

Probe

up to +200°C

copper, Mat. Ref. 2.0090
electrotinned 1.5 mm dia.

copper, Mat. Ref. 2.0090
electrotinned brazed

up to +300°C

copper, Mat. Ref. 2.0090
electrotinned 1.5 mm dia.

stainless steel,
Mat. Ref. 1.4571 brazed

up to +500°C

stainless steel,
Mat. Ref. 1.4571
1.5 mm dia.

stainless steel,
Mat. Ref. 1.4571 welded

up to +300°C

stainless steel,
Mat. Ref. 1.4571
1.5 mm dia.

stainless steel,
Mat. Ref. 1.4571 welded

TW

in upper third of scale

+0

%

-4

at scale start

+0

%

-6

STW

in upper third of scale

+0

%

-5

at scale start

+0

%

-7

Surface-mounting thermostats with end of scale

< +200°C

≥ +200°C ≤ +350°C

> 350°C

TW

STW

TW

STW

TW

STW

on thermostat head %/°C

0.08

0.17

0.06

0.13

0.14

0.12

on capillary %/°C per meter

0.047

0.054

0.09

0.11

0.04

0.03