6 Instrument description

18

Permissible
probe temp.

max. limit +15% (+550°C with limit > 450°C)

Permissible
storage temp.

max. +50°C, min. -20°C

Housing

black polyester housing, glassfiber-reinforced
with lead-sealable screws

Connection
cable

diameter 6 to 12 mm, conductor cross-section up to 2.5 mm

2

Switching
differential
in % of
control/limit
range

Contact rating

5 A, 230 V AC +10%, p.f.

≥ 0.9

Fuse required

see contact rating

Protection

EN 60 529 - IP65

Operating
medium

water, oil, air, superheated steam

Time constant
t

0.632

Action

to EN 60 730-2-9, DIN EN 14597

TW:

2BL

STW:

2BKLNP

Nominal
position (NL)

to DIN 16527, NL 0 — NL 90 (other NL on request)

Weight

approx. 0.6 kg

Thermostats with end of scale

≤ 350°C

Thermostats with end of scale

> 350°C

Switching

action

Nominal

value

Possible

measured

value

Switching

action

Nominal

value

Possible

measured

value

TW

3

3-5

TW

5

5-9

STW

5

5-7

STW

6

6-11

in water

in oil

in air / superheated

steam

≤ 45 sec

≤ 60 sec

≤ 120 sec