4 Installation

4.2

Electrical connection

✱ Open the housing.

➈ Chapter 3.2 "Opening the surface-mounting thermostat", page 8

✱ Pass the connection cable (6 to 12 mm cable dia.) through the

Ex cable gland (1).
➈ Chapter 3.1 "Dimensions", page 7

✱ Make the connection to the terminals (2) in accordance with the connection

diagram.

✱ Fitting type X (no special tools).
✱ The connecting cable must have a fixed installation.

✱ Position connection cable in the housing and tighten the Ex cable gland (1)

using the tightening torque given below:
➈ Chapter 3.1 "Dimensions", page 7

✱ Replace the protective cap on the terminal block.

4.3

Connection diagrams

✱ Connect the protective earth conductor to the PE terminal.

Screw-in thread (1.1) into housing

= 3.75 Nm

Compression screw (1.2)

= 3.50 Nm for 6 mm cable dia.

Compression screw (1.2)

= 2.50 Nm for 12 mm cable dia.