6 configuration – JUMO 705021 mTRON T - Analog Input Module, 8-Ch. Operating Manual User Manual

Page 44

background image

6 Configuration

44

Alarms/

Faults

CAlarm/Fault

System collective alarm or system fault (cen-
tral processing unit and modules)

CAlarm/Fault ackn.

System collective alarm or system fault with
acknowledgement
Signal remains active until acknowledgement.

CAlarm device

System collective alarm (central processing
unit and modules)

CAlarm ackn.

System collective alarm with acknowledge-
ment
Signal remains active until acknowledgement.

Fault

System fault (central processing unit and mod-
ules)

Fault ackn.

System fault with acknowledgement
Signal remains active until acknowledgement.

CAlarm Basis

Central processing unit collective alarm

System Run

System state (Run = 1, Stop = 0)

Reserve 1

(Reserved for future use.)

Fieldbus error

Error at fieldbus interface

System error mandatory

Error in a mandatory module

System error optional

Error in an optional module

No PLC

No PLC program available

Battery empty

Battery alarm (central processing unit buffer
battery is dead and must be replaced)
Notify service department!
Attention: RAM memory content is deleted!

Battery low

Battery pre-warning (central processing unit
buffer battery can be replaced within 4 weeks
without data loss)
Notify service department!