2 analog inputs, 3 digital input, 4 functional test – JUMO 705021 mTRON T - Analog Input Module, 8-Ch. Operating Manual User Manual

Page 26: Digital input, Functional test, 4 electrical connection, 2 analog inputs 4.3.3 digital input

background image

4 Electrical connection

26

4.3.2

Analog inputs

4.3.3

Digital input

4.4

Functional test

The voltage supply must be tested on completion of the electrical connection:

Startup

The check described above completes the process of installation and electrical connection. For
startup, use the additional documentation (operating manual or system manual).
The "Introduction" section of this document contains an overview of all documentation for the
measuring, control, and automation system.

Connection

Input

Terminals

Symbol and terminal designation

RTD temperature probe

2-wire circuit

1

2

3

4

5

6

7

8

1 and 2

3 and 4

5 and 6

7 and 8

9 and 10

11 and 12

13 and 14

15 and 16

1, 3, 5, 7, 9 , 11, 13, 15

2, 4, 6, 8, 10,12, 14, 16

Connection

Input

Terminals

Symbol and terminal designation

Digital input DC 0/24 V

1

17 and 18

17

18

U

+

-

x

Signal

Meaning

LED "P" (Power, green) is lit

The module is being supplied with voltage
through the side contacts.

LED "P" (Power, green) is not lit

The module is not supplied with voltage or there
is a problem with the electrical function of the
LED.
Remedy:

Check the voltage supply to the side contacts
of the preceding module (top contact +24 V,
bottom contact GND).

Check voltage supply at the "+24 V" and
"GND" terminals of the base unit or router
module.

Check power supply unit and connection be-
tween the power supply unit and the base unit
or router module.

If the "Power" LED does not light up despite a
voltage supply being present, the module insert
or – if the bus board inside the case is faulty – the
entire module must be replaced.