beautypg.com

1 alarms, 6 configuration – JUMO 705021 mTRON T - Analog Input Module, 8-Ch. Operating Manual User Manual

Page 34

background image

6 Configuration

34

6.2.1

Alarms

Limit value monitoring with one or two alarms and various alarm types can be activated for each
analog input. In addition, this function is required in order to trigger the collective alarm of the
module if the event of deviation above or below the measuring range (out of range).

Setup dialog

Parameter

Parameter

Selection/settings

Description

Alarm type 1, 2

Off

Monitoring is not active.

Min. alarm

Alarm is issued if the limit value is not
met.

Max. alarm

Alarm is issued if the limit value is
exceeded.

Limit value 1, 2

-99999 to 0 to +99999

Limit value at which an alarm is issued.

Kind of alarm 1, 2 The alarm type is not set by default.

Collective alarm

Alarm results in collective alarm of the
module.

Event

Alarm results in an entry (event text) in
the event list.

Event text 1, 2

Use default text or select other text from
the list.

Text that is entered in the event list for
an alarm (if Alarm type = "Event").

Switching differ-
ential

0 to 99999

Used to suppress constant switching
operations in the event of minor fluctua-
tions of the input signal around the limit
value.

Alarm suppres-
sion

Digital selector (Inactive)

Chapter 6.1 "Digital selector", page
31

Signal to activate the alarm suppression

Alarm delay

0 s to 65535 s

Delay time for alarm activation

?

?

?