1 alarms, 6 configuration – JUMO 705021 mTRON T - Analog Input Module, 8-Ch. Operating Manual User Manual
Page 34
6 Configuration
34
6.2.1
Alarms
Limit value monitoring with one or two alarms and various alarm types can be activated for each
analog input. In addition, this function is required in order to trigger the collective alarm of the
module if the event of deviation above or below the measuring range (out of range).
Setup dialog
Parameter
Parameter
Selection/settings
Description
Alarm type 1, 2
Off
Monitoring is not active.
Min. alarm
Alarm is issued if the limit value is not
met.
Max. alarm
Alarm is issued if the limit value is
exceeded.
Limit value 1, 2
-99999 to 0 to +99999
Limit value at which an alarm is issued.
Kind of alarm 1, 2 The alarm type is not set by default.
Collective alarm
Alarm results in collective alarm of the
module.
Event
Alarm results in an entry (event text) in
the event list.
Event text 1, 2
Use default text or select other text from
the list.
Text that is entered in the event list for
an alarm (if Alarm type = "Event").
Switching differ-
ential
0 to 99999
Used to suppress constant switching
operations in the event of minor fluctua-
tions of the input signal around the limit
value.
Alarm suppres-
sion
Digital selector (Inactive)
Chapter 6.1 "Digital selector", page
31
Signal to activate the alarm suppression
Alarm delay
0 s to 65535 s
Delay time for alarm activation
?
?
?