JULABO SL-26 Heating Circulators User Manual
Page 71

HL / SL
71
9.9.3.
Input of the connector - REG+E-PROG
 
 
Menu >Configuration< 
1.
2.
Menu >Inputs/Outputs<
3.
E-PROG - Input
Setting is necessary if
1. the Setpoint is to be set via an external voltage or current source or
programmer 
For this, in the menu >Configuration<, first set the menu item 
>Setpoint< to >Eprog<. 
2. the heater variable should be controlled via an external control
pulse. 
For this, in the menu >Configuration<, set the menu item > 
ActVar.< to >Eprog<. 
 
3. the signal of an external flow meter should be registered.
The E-Prog input can only be used either under menu item 
>Setpoint< or under menu item > Actvar <. 
If the input is occupied neither by >Setpoint< or > ActVar <, the 
signal of a flow meter can be connected. 
First set menu >Configuration<, then menu >Inputs/Outputs<. 
 
 
 
 
 
 
 
 
 
Example: 
 
Connect the external voltage or current source or programmer to 
the REG+E-PROG socket (12) of the circulator. 
Selecting the signal:
The programmer (E-PROG) input of the circulator can be matched 
to the output signal of the external voltage or current source. 
Voltage 
voltage
input
Current
current
input
“L Value” - Setting the LOW value: (See below
)
First adjust and set the lowest voltage or current on the external 
voltage or current source (e.g., 0 V or 0 mA). 
Then after approx. 30 seconds, enter the corresponding 
temperature value (e.g., 20.00°C).on the circulator by pressing the 
appropriate keys on the keypad and press
to set.
“H Value” - Setting the HIGH value: (See below
)
First adjust and set the highest voltage or current on the external 
voltage or current source (e.g., 10 V or 20 mA). 
Then after approx. 30 seconds, enter the corresponding 
temperature value (e.g., 300 °C).on the circulator by pressing the 
appropriate keys on the keypad and press
to set.
 
 
Example:
Set the external voltage or current source output for the equivalent 
of a 50 °C temperature setpoint. 
The value adjusted and set on the external programmer is 
displayed in line 4 of the LCD DIALOG-DISPLAY for inspection. 
