Table 4-3remote mode, Table 4-4program mode, Rs-3000 – INFICON RS-3000 Power Supply Controller User Manual
Page 20
instruments
Power Supply Controller
RS-3000
Table 4-3
Remote Mode
Event From
To
Description
RMT key
O.F.F. mode
REMOTE mode
Starts Remote mode. RS-3000 needs to be
connected to an STC-2000 or equivalent. The large
display shows current and the small display shows
kilowatts. The RMT indicator is illuminated.
RMT key
REMOTE mode
MAN mode
Toggles Remote mode off and automatically starts
the Manual mode (see Manual mode START)
retaining the last current value held in the Remote
mode. As previously described for the START key
event entering Manual mode, the large display shows
current and the small display alternates between
showing kilowatts and minutes. The RMT indicator is
now off and the MAN indicator is illuminated.
STOP key
REMOTE mode
O.F.F. mode
Ends Remote mode. The pendant STOP key
provides this same function.
Table 4-4
Program Mode
Event From
To
Description
PRGM key
any mode (except
the PRGM mode)
PRGM mode
Starts Program mode. The PRGM indicator blinks
while in the Program mode. The first in a
sequence of six user programmable parameters is
shown (that of maximum current). The INC/DEC
keys provide the means to make a value change.
PRGM key
PRGM mode
PRGM mode
For the 2
nd
press of the PRGM key while in the
Program sequence, Ramp minutes can be altered
by the INC/DEC keys (range is 0-99.9 minutes).
For the 3
rd
press of the PRGM key while in the
Program sequence, Ramp current can be altered
by the INC/DEC keys (range is 0-600 Amps). For
the 4
th
press of the PRGM key while in the
Program sequence, beeper configuration can be
altered by the INC/DEC keys (select: ON or OFF).
For the 5
th
press of the PRGM key while in the
Program sequence, communication speed can be
configured by the INC/DEC keys (9.6, 38.4 or 115
kbaud). For the 6
th
press of the PRGM key while in
the Program sequence, address can be
configured by the INC/DEC keys (0-9). The 7
th
press of the PRGM key while in the Program
sequence, terminates the PRGM mode and the
PRGM indicator ceases to blink. Parameters are
saved immediately as they are entered (there is
no quit without saving). If there is a lack of activity
for 30 seconds during the programming sequence,
the programming mode will auto-terminate.
Section 4
Page 4 - 3
Specifics