IMMERSION WELLS

When installed on an Electro-Well™ (sold separately), the Low
Water Cut-Off function is automatically activated. Heat transfer
grease should not be used. NOTE: For proper operation, there must
be 1/2" clearance between the copper well tube and any furnace
within the boiler.

See Electro-Well™ models on page 15.

When installing on a standard immersion well, the LWCO func-
tion should be turned off
(see page 9 for instructions). A buildup of
heat transfer grease or other coatings in older wells can interfere
with continuity between the sensor and the well causing a false low
water shutdown. Turning off the LWCO function will prevent this
from occurring.

Fuel Smart HydroStat can be installed on a Hydrolevel Electro-Well™ or on an existing immersion well already in the boiler.

IMPORTANT: The control will only provide low water cut-off protection when installed on an Electro-Well™.

Installing HydroStat

with Hydrolevel Electro-Well

Installing HydroStat

with Standard Immersion Well

HydroStat 3200-Plus Instructions: