Heidolph MR Hei-End User Manual
Page 41

39
E
Write commands
OUT_SP_1 y
Enter set temperature, medium/hotplate in
°C
OUT_SP_2 y
Enter set safety temperature “deltaT” in °C
OUT_SP_3 y
Enter set motor speed in rpm
OUT_MODE_2 y 0 = all OFF after power return
1 = heating / stirring ON after power return
(set points are obtained)
„o“
„*“
General commands
START_1
Start heater control, activate remote
–
alternating display *Remote*
Note: the keypad is disabled when
in remote mode.
START_2
Start motor, activate remote
– alternating
display *Remote*
STOP_1
Stop heater control
STOP_2
Motor speed=0 MotorStop
RESET
Reset to initial state
– heater off, motor off,
exits remote mode
STATUS
Request status
0 = ManualMode
1 = RemoteMode Start
(START_1 OR
START_2)
2 = RemoteMode Stop
(STOP_1 AND
STOP_2)
<0 Error code in case of
fault