beautypg.com

3 phase, 3 phase 1 phase – Flint & Walling Constant Pressure Pumping Stations - end suction centrifugal pumps User Manual

Page 4

background image

4

95 North Oak Street • Kendallville, IN 46755

Copyright 2012. All Rights Reserved.

SINGLE PHASE

Distance From Motor

To Fuse Box Meter,

or Electrical Outlet

Recommended Copper Wire Size

1HP

1-1/2 HP

2 HP

3 HP

5 HP

100 ft.

115V

230V

10
14

8

12

8

10

*
8

-

6

150 ft.

115V

230V

6

12

6

12

4

10

*
8

4

200 ft.

115V

230V

6

12

6

10

4
8

*
6

-

4

300 ft.

115V

230V

*

12

*
6

*
6

*
4

-

2

500 ft.

115V

230V

*

10

*
4

*
4

*
2

-

0

(*) Not economical to run at 115V, use 230V.
Figure 3

THREE PHASE

Distance From

Motor To Fuse

Box Meter, or

Electrical Outlet

Recommended Copper Wire Size

1HP

1-1/2

HP

2 HP 3 HP 5 HP

7-1/2

HP

100 ft.

230V
460V

14
14

12
12

12
12

12
12

10
12

8

12

150 ft.

230V
460V

14
14

12
12

12
12

10
12

8

12

6

12

200 ft.

230V
460V

14
14

12
12

12
12

10
12

8

12

6

12

300 ft.

230V
460V

12
14

12
12

10
12

8

12

6

10

4

10

500 ft.

230V
460V

10
14

10
12

8

12

6

10

4
8

2
8

Figure 4

MOTOR PROTECTION

WARNING: Never examine, make wiring changes

or touch the motor before disconnecting the main

electrical supply switch.
1.

Motors may or may not have built-in thermal
overload protection depending upon the
horsepower size, phase, type and motor
manufacturer. Refer to the motor nameplate for
overload protection information. It is recommended
that a properly sized magnetic or manual starter
(both with properly sized heaters) be used with all
motors. Install starters following instructions of the
starter manufacturer. See Figure 8 & 9 for magnetic
starter wiring diagram. See Figures 5, 6 & 7 for
motor diagrams.

2. All motors (single and three phase) should be

equipped with a correctly fused disconnect switch
to provide protection. Consult Local or National
Electrical Codes for proper fuse protection based on
motor nameplate.

3. Under size wiring can cause motor failure (low

voltage), frequent cut-out of motor overload
protector, television interference and even fire.
Make certain the wiring is adequately sized (Figure
3 & 4), well insulated and connected to a separate
circuit outside the building in case of fire.

IL1229

6

5

4

3

2

1

7

8

9

6

5

4

7

8

9

3

2

1

HIGH VOLTAGE

LOW VOLTAGE

LINE

LINE

3 Phase

Figure 5 - Wiring Diagram for Baldor TEFC 3 Phase

motors

6

5

4

3

2

1

7

8

9

6

5

4

7

8

9

3

2

1

(4)

(10)

(9)

(3)

(2)

(4)

(10)

(9)

(3)
(2)

IL1230

HIGH VOLTAGE

LOW VOLTAGE

HIGH VOLTAGE

LOW VOLTAGE

LINE

LINE

BROWN

LINE

VIOLET

BLACK

YELLOW

BLUE

BROWN

LINE

VIOLET

BLACK

YELLOW

BLUE

3 Phase

1 Phase

Figure 6 - Wiring Diagram for Franklin Electric TEFC 1 Phase

and 3 Phase motors

IL1231

T6

T5

T4

T3

T2

T1

T7

T8

T9

T6

T5

T4

T7

T8

T9

T3

T2

T1

T2

T5

T8

T6

T3

T7 T1

HIGH VOLTAGE

LOW VOLTAGE

GROUND

(WHEN REQ)

LINE

LINE

3 Phase

Figure 7 - Wiring Diagram for Marathon TEFC 3 Phase

motors