WIRE SIZE CHART

Distance From

Motor To Fuse

Box, Meter or

Electrical Outlet

Minimum Copper Wire Size Chart (Gauge)

Single Phase Motors

1 HP

1-1/2 HP

2 HP

115

Volt

230

Volt

115

Volt

230

Volt

115

Volt

230

Volt

0-50 Ft.

50-100 Ft.

100-150 Ft.
150-200 Ft.
200-300 Ft.

Fuse Size (Amps)

12
10

8

*
*

30

14
14
12
12
10
15

12
10

8

*
*

30

14
14
12
12
10
20

12
10

8

*
*

30

14
14
12
10
10
20

(*)

Not economical to run in 115V, use 230V

PUMP ELECTRICAL INSTRUCTIONS

WARNING

ELECTRICAL SHOCK ALERT.

Under-size wiring can cause motor failure and

even fire. Use proper wire size specified in the

wire size chart.

ELECTRICAL SHOCK ALERT.

Replace damaged or worn wiring cord immediately.

ELECTRICAL SHOCK ALERT.

Do not kink power cable and never allow the cable

to come in contact with oil, grease, hot surfaces, or

chemicals.

ELECTRICAL SHOCK ALERT.

The pump must be properly grounded using

the proper wire cable with ground.

ELECTRICAL SHOCK ALERT.

Always disconnect pump from electricity

before performing any work on the motor.
WARNING

ELECTRICAL SHOCK MAY OCCUR

All wiring should be performed by a qualified

electrician in accordance with the National Electric

Code and local electric codes.

ELECTRICAL SHOCK MAY OCCUR

Connect the pump to a separate electrical circuit

with a dedicated circuit breaker. Reference the wire

size chart below for proper fuse size.

ELECTRICAL SHOCK MAY OCCUR

Protect the power cable from coming in contact with

sharp objects.

PRODUCT DAMAGE MAY RESULT

Make certain that the power source matches

the pump requirements. This pump has a dual

voltage motor and can run on 115 V or 230 V.

This pump is wired from the factory to run on

230 volts; refer to Electrical Instructions if you

want to change the pump to run on 115 volts.