5 Mounting

Mounting must be performed only by authorized personnel.

To achieve the degree of protection IP 67, it is necessary to install the Electronic-Key adapter in a
clean, flat metal plate at least 2 mm thick and to tighten the screws to a tightening torque of at least
0.25 Nm.

The Electronic-Key adapter is intended for mounting in control panels with a cut-out measuring
33 mm x 68 mm according to DIN 43700 (see page 8 chapter 4.1 Dimension drawing, Electronic-Key
adapter/front panel cut-out)
. The device is fastened using screw clamp elements from the rear side of the panel.

The screw clamp elements for front panel mounting are included with the Electronic-Key adapter.

1. Insert Electronic-Key adapter, with seal already bonded in place, into the mounting cut-out from the front.

2. Insert screw clamp elements in the housing of the Electronic-Key adapter and tighten to min. 0.25 Nm.

After mounting, again check the Electronic-Key adapter for firm seating and correct sealing of the front
plate.